DGS-8800e

Digital Governor System, DGS-8800e
Sulzer RTA engines
Denis version


Instruction Manual





Department/Author:        Approved by:


___________________        ____________________

Øyvind Tellefsen        Morten Hasås





 2025 KongsbergNorcontrol as

All rights reserved

No part of this work covered by the copyright

hereon may be reproduced or otherwise copied

without prior permission from

Kongsberg Norcontrol as























-Intentionally left blank-





DOCUMENT STATUS


Issue No.

Date/Year

Inc. by

Issue No.

Date/Year

Inc. by

P0

31-Aug-93

GAM




A

27-Jun-94

BGJ




B

16-Feb-98

MOH




































CHANGES IN DOCUMENT


Issue

ECO

Paragraph

Paragraph Heading/

No.

No.

No.

Description of Change

A



First issue

B

AAE 000034


Document updated, NSD ch. to WNSCH











































































TABLE OF CONTENTS


Section        Page

1.        System Description        1

1.1        Introduction        1

1.1.1        Regulator functions        2

1.1.2        Actuator Function        2

1.1.3        System configuration        3

1.2        System Units        4

1.2.1        Digital Governor Unit, DGU        4

1.2.2        Digital Servo Unit (DSU)        5

1.2.3        TRAFO 001        6

1.2.4        Electric actuator, ELACT 001        7

1.2.5        Equipment Location        8

1.3        Main Specification        8

1.3.1        Input and output data-channels        8

1.3.2        Logic input signals        8

1.3.3        Power Positioning Characteristics        9

1.4        Mode selections        10

1.4.1        NORMAL mode        10

1.4.2        IDLE mode        10

1.4.3        CONSTANT FUEL mode        10

1.4.4        ROUGH SEA mode        11

1.4.5        SETPOINT mode        11

1.4.6        TEST mode        11

1.4.7        CALIBRATION mode        11

1.4.8        SELFTEST mode        12

1.5        Programmable functions        13

1.6        Programming characteristics        14

1.7        Regulator main functions        15

1.7.1        RPM Controller Function        16

1.7.2        RPM Command Function        17

1.7.3        RPM Measurement Function        18

1.7.4        Regulator Gain Function        19

1.7.5        Fuel Limiting Function        20

1.8        Actuator Main Functions        21

1.8.1        Fuel Actuating Function        21

1.8.2        Servo Control function        21

2.        System Operation        22

2.1        Regulator Operator Panel        22

2.1.1        Panel Layout        22

2.1.2        Regulator Indicator Lamps        23

2.1.3        Regulator Mode Lamps        23

2.1.4        Regulator STATUS lamps        24

2.1.5        Regulator ALARM/WARNING lamps        24

2.2        Parameter and Data Areas        25

2.2.1        Parameter Up/Down        25

2.2.2        Data value Up/Down        26

2.2.3        Change Lock        26

2.2.4        Service code        26

2.2.5        Save        26

2.3        Regulator Operating Buttons        26

2.3.1        Constant Fuel Mode Button        27

2.3.2        Rough Sea Button        27

2.3.3        Fuel Setpoint Button        28

2.3.4        Regulator Test Buttons        28

2.4        Actuator Operating Panel        30

2.4.1        Actuator Indicator Lamps        30

2.4.2        Actuator MODE lamps        30

2.4.3        Actuator STATUS lamps        30

2.4.4        Actuator ALARM lamps        31

2.4.5        Actuator Parameter and Data Areas        32

2.4.6        Actuator Operating Buttons        33

2.4.7        Actuator Test Buttons        34

2.5        Procedures        35

2.5.1        Power On        35

2.5.2        Power Off        35

2.5.3        Start Command        35

2.5.4        Transfer Command between remote control and back-up control        36

2.5.5        Stop Command        36

2.5.6        Fuel Setpoint Emergency Control        36

3.        Trouble Shooting        37

3.1        Alarms / Warnings        37

3.2        Regulator Alarms        37

3.2.1        System in Test        37

3.2.2        Low Voltage Alarm        38

3.2.3        RPM Detector Failure        39

3.2.4        In-Data Error on Regulator        40

3.2.5        Out Data Error        40

3.3        Actuator Alarms        41

3.3.1        Feedback Failure        41

3.3.2        Indata Error on Actuator        41

3.3.3        Servo Amplifier Failure        42

3.3.4        System in Test on Actuator        42

3.4        Special Messages        43

3.4.1        " -- e r r o r "        43

3.4.2        " -- l o a d "        44

3.4.3        " 88 888888 "        44

3.4.4        Freeze        44

3.5        Actuator Unit        44

3.5.1        Unstable servo        44

4.        Adjustments        45

4.1        START-UP        45

4.1.1        Power-Up        45

4.1.2        Adjust BASIC parameters.        46

4.1.3        Actuator zero adjustment        47

4.1.4        Fuel Output Signals (Option)        48

4.1.5        RPM detectors        48

4.2        Regulator parameter description.        49

4.2.1        Regulator parameter adjustments        49

4.2.2        Regulator input signal adjustment        49

4.2.3        Digital signals        49

4.2.4        Analog signals        49

4.2.5        OpCode 0 Parameters.        50

4.2.6        OpCode 1 Parameters.        51

4.2.7        Engine Data.        51

4.2.8        RPM Cmd Limiting        54

4.2.9        Measured RPM Filters        57

4.2.10        Speed Controller Response        58

4.2.11        Fuel Setpoint        60

4.2.12        Fuel Limiters        61

4.2.13        Actuator type setting.        62

4.2.14        Dead band mode or constant fuel mode        64

4.2.15        Various parameters. (Stop signal, Cancel limiters,,,)        66

4.2.16        Alarm Adjustments        67

4.2.17        Dual Rpm Command Instruments. Digital fuel limiter output signal.        68

4.2.18        Non Linear Compensation Due To Fuel Pump Position        69

4.2.19        Shaft Generator Function.        69

4.2.20        Non Linear Compensation Due To Low RPM        70

4.2.21        QPT        71

4.2.22        Test        71

4.3        Actuator parameter description        73

4.3.1        Mode selection.        73

4.3.2        Readable information.        73

4.3.3        Alarm info, info reset and feedback failure block reset.        73

4.3.4        System parameter.        74

4.3.5        Actuator Control Parameters.        74

4.3.6        Servo Position Feedback Fail Test.        75

4.3.7        Idle mode, manual control.        76

4.3.8        Actuator operating range.        77

4.3.9        Alarm Relay.        77

4.3.10        Digital input signals.        78

4.3.11        Block when low voltage.        78

4.3.12        Actuator rotation direction.        78

4.3.13        Fuel indication output signal.        79

4.3.14        Test parameters.        79

4.3.15        Readable parameters.        79

5.        Maintenance        81

5.1        Visual Inspections        81

6.        APPENDIX        83

6.1        Appendix A, Input and output signal list for DGS-8800e        83

6.2        Appendix B *** Dip-Switches        84

6.3        Appendix C *** Digital Inputs on Regulator        85

6.4        Appendix D *** Analog Inputs on Regulator        86

6.5        Appendix E *** Digital Inputs on Actuator        87

6.6        Appendix F *** Hexadecimal Counting        88

6.7        Appendix G *** Jumpers on NN-791.12 I/O Processor Board.        89

6.8        Appendix H *** Layout for NN-791.12 I/O Processor Board.        90

6.9        Appendix I *** Jumpers on NA-1105        91

6.10        Appendix J *** Back-wiring        92

7.        Related Documents.        92

7.1        SBS Servo Amplifier Manual (Parvex).        92

7.2        DGS 8800e Parameter List. (KNCA, AA-0089.DOC)        92




TABLE OF FIGURES

Section        Page


Figure 1.1 System configuration.        3

Figure 1.2 Digital Governor Unit DGU 8800e        4

Figure 1.3 DSU, Servo amplifier and power unit's        5

Figure 1.5 Transformer        6

Figure 1.6 Electric actuator - ELACT 001        7

Figure 1.7 DGU 8800e Block Diagram.        15

Figure 1.8 Governor functions.        16

Figure 1.9 RPM Command Function.        17

Figure 1.10 RPM Measuring Function.        18

Figure 1.11 Regulating Gain Function.        19

Figure 1.12 Fuel Limiting, Non Linear Compensation and Output Scaling Function        20

Figure 1.13 Servo Control Function        21

Figure 2.1 Operator Panel        22

Figure 2.2 Indicator lamps.        23

Figure 2.3 Regulator Parameter and Data Areas.        25

Figure 2.4 Regulator Operation Buttons.        28

Figure 2.5 Regulator Test Buttons.        29

Figure 2.6 Actuator Indication lamps.        30

Figure 2.7 Actuator Parameter and Data Areas.        32

Figure 2.8 Actuator Operation Buttons.        33

Figure 2.9 Actuator Test Buttons.        34

Figure 4.1 Rotation of actuator. (CW = Clock Wise, CCW = Counter Clock Wise).        47

Figure 4.2 Actuator Arm.        52

Figure 4.3 Critical speed. Blocked areas.        56

Figure 4.5 Constant fuel mode.        65

Figure 4.6 Non Linear compensation due to low speed.        70

Figure 4.7 Actuator position timing.        72

Figure 4.8 Actuator Gain.        74

Figure 4.9 Timeout for too slow.        76

Figure 4.10 Actuator position,        79

Figure 6.1 Dipswitches.        84

Figure 6.2 Digital inputs on regulator.        85

Figure 6.3 Analog inputs on regulator.        86

Figure 6.4 Processor board layout.        90

Figure 6.5 NA-1105, Acyncron Buffer layout.        91


1.                                            System Description

1.1                                            Introduction

The Digital Governor System (DGS-8800e) is a complete package which fulfills all tasks for governing the speed of low-speed, long-stroke diesel engine of the Sulzer RTA type manufactured by Wärtsila NSD and their licencees. The speed setting may be from three different systems, usually the remote control system (AutoChief 4 or AutoChief 7), local control panel, and control room back-up panel (optional).


The system may be fitted to both fixed pitch and controllable pitch propeller systems (FPP and CPP systems). The system responds to slow-down and shut-down signals from external safety systems. Fuel-saving features, such as load limiting functions, are included.


The DGS 8800e performs computerized handling of all measurements and control signals. It includes panel push-button flexibility to select, adjust, and test the system performance. Movement of the fuel rack is done by an electric actuator, with a 3 phase brushless servomotor as the power medium.


The main purpose of the DGS 8800e system is to control the position of the engine fuel servo, in order to maintain an engine speed equal to a reference setting. The system is composed of two separate and self-contained subsystems, the speed Regulating Function, and the fuel Actuator Function.


The speed pick-up sensors are of an inductive type, mounted towards engine gearwheel inside the main engine. They are completely duplicated for increased system reliability.


Engine charge air pressure is measured to be able to limit the fuel injection according to charge air pressure value.


For CCP systems, the pitch value is input to compensate for loading conditions.


The speed reference input to the system may be one of three, selectable either from the remote control system (from bridge or control room), the local control panel, or the control room back-up panel.


The DSU (Digital Servo Unit) which is supplied from the AC mains, supplies the DGS 8800e system with 24V DC.


The ELACT (Electric Actuator) is supplied by a 3 phase AC main power supply through a TRAFO 001 (transformer) and the DSU with power and servo amplifier. The Actuator Feedback Transducer is a high resolution absolute encoder with contactless displacement to improve system reliability.


1.1.1       Regulator functions


The main purposes are:


        Speed reference computation.

        Speed measurement and filtering.

        Output and limit the command signal to the fuel actuating function.


In addition, the Regulating Function has several sub-functions, such as:


        Displaying data values.

        Programming user-dependent parameters.

        On-line testing.

        Off-line testing.

        Selection of alternative mode operations.


1.1.2       Actuator Function


The main purposes are:


        Sense the actuator position command from the Regulator.

        Positioning the actuator (and fuel-rack) according to commanded value.


In addition, the Actuating Function contains several secondary functions:


        Limiting speed of fuel-rack.

        Output for fuel-rack (actuator) indication (option).

        Displaying data values.

        Repeatedly testing of System failures.


1.1.3       System configuration


This configuration drawings shows the DGS-8800e with the belonging accessories, arrangement is in accordance with the Denis specifications issued by Wärtslia NSD (Denis-1, Denis-5 and Denis-6).


img1


Figure 1.1 System configuration.


1.2                                            System Units

The DGS 8800e Digital Governor System consists of these basic units:


        a)        DGU 8800e Digital Governor Unit.


        b)        DSU, Digital Servo Unit.


        e)        TRAFO 001, Transformer, interface between mains and DSU.


        f)        ELACT 001, Electric actuator.


1.2.1       Digital Governor Unit, DGU

The DGU (Fig.1.2) fits into standard 19 inch rack. It has internal Power Module for low-voltage distribution. The panel section allows direct operator control of system functions. The signals from process are all connected to standard terminal boards, with easy flat-cable connection into the unit.


The process signals are adapted to digital data through individual plug-in adapters, with options for all standard signal formats.


img2

Figure 1.2 Digital Governor Unit DGU 8800e


1.2.2       Digital Servo Unit (DSU)

The ABS power unit, SBS servo amplifier and 24V DC power supply for the DGU 8800e are mounted in cabinet for installation on wall in the engine control room.


The servo amplifier together with the power unit are the electric actuator's control electronic and controls the electric actuator speed.

 

img3

Figure 1.3 DSU, Servo amplifier and power unit's


1.2.3       TRAFO 001

The Trafo 001 is a transformer unit that supplies the electric actuator's power amplifier with 135 V AC for speed control of the electric actuator.


The transformer has 220V AC, 230V AC or 440V AC input and 135V AC output. It is specified to deliver up to 3.6 kVA continuously. 110VAC or other input voltage transformer may be delivered on request.






img4

Figure 1.5 Transformer


1.2.4       Electric actuator, ELACT 001

The actuator system comprises a brushless servomotor type Parvex LS 620 EL, with a reduction gear type Cyclo FABS 25/89. The servomotor is electro-mechanical and contains no electronic components. It has ball bearings which are lubricated for life. The system is certified for protection degree IP65, precision class N and insulation class F. The servomotor is controlled by servo amplifier Parvex SBS 15/30A. The servomotor has a built-in brake which activates if a failure such as system failure or power failure occurs, and will keep the fuel rack at the current position, i.e. fail-safe condition, as the engine will continue to run at it's previous speed. A thermal protection device is also included in the servo motor. The fuel index (or actuator position) is measured with an absolute encoder, mounted directly on the servomotor. The fuel actuator is to be mounted and connected the fuelrack of the main engine in accordance with drawings issued by Wärtsila NSD.


img5



Figure 1.6 Electric actuator - ELACT 001


1.2.5       Equipment Location

The DGU unit is to be located in the control room console, and should be mounted in the vertical section of the console.


The DSU cabinet is a standard wall-mountable box, which should have less than 25 m cabling distance from the actuator.


The Actuator is mounted on the engine and is connected to fuel linkage in accordance with drawings issued by Wärtsila NSD.



1.3                                            Main Specification

1.3.1       Input and output data-channels


a)        Two speed inputs signal from two inductive pick-up's delivered by the engine builder, and mounted as spesified by WNSCH. One set of duplicate channel. Measures speed up to more than 300 rpm. Which handles engines from the smallest RTA48 to the largest RTA96C. Minimum frequency of approximately 4 Hz, depending of max. speed and number of pulses received from the speed pick-ups.

b)        Three speed command inputs, 4-20 mA current, 0-10 V, or from 5K         potentiometer.

c)        One charge air pressure signal, 0-4 bar, 4-20 mA.

d)        Pitch feedback signal, 5K potentiometer or -10 to +10 V (for CPP installations).

d)        Two output signals, reflecting engine fuel index (load indicator). Output signal

        are 4-20 mA or 0 - 10 VDC.

        NOTE: These signals are a copy of the actuator position.

g)        Start diesel signal (active when shaftgen. is active and speed command is

        reduced). (Optional feautre)


1.3.2       Logic input signals


a)        External stop (shut down) signal from external safety system.

b)        Three binary (on/off) command position selection signals, selecting which of the three speed command signals that are to be used.

c)        Slow-down signal from external safety system.

d)        Zero fuel order from each of the three command positions (to be active when STOP, i.e. zero fuel is ordered).

e)        Power-failure signal from remote control system (speedset freeze at last engine running speed).

f)        Back-up RPM (for CPP installations only).

g)        Heavy start (or increasing fuel limiters) from remote control system and from switch in control room.


1.3.3       Power Positioning Characteristics


Power positioning characteristics:

ELACT-001

Maximum output power torque (nominal)

360 Nm

Maximum output power torque (nominal)

720 Nm

Static accuracy*

0.1 mm

Maximum speed*

372 mm/sec

Stroke w/ 140 mm arm (angle 42°)*

100 mm*

Controllable angle

42°


*        At operating angle 42, 140 mm. actuator arm, giving a max. stroke of 100 mm.


1.4                                            Mode selections

The descriptions given in the following paragraphs are valid both for Regulator and Actuator parts. The actual system mode is shown on the upper left indicator panel on front of DGU.


1.4.1       NORMAL mode

This mode indicates normal running mode of the system. The transfer to this mode is done automatically by the maneuvering handle. All adjustments of system parameters is allowed also saving (kept after powering down) is done. Monitoring of all system data values may be done by appropriate parameter number (refer commissioning parameter list).


1.4.2       IDLE mode

This mode is automatically selected after powering up system. In this condition, the actual real time processing of governor is not critical. The ultimate condition to stay in this mode, is for the that STOP is ordered (zero fuel order signal is ON).


Reprogramming of parameter values can be done.


NOTE:        Automatic transfer to Idle when system is in STOP status.


1.4.3       CONSTANT FUEL mode

This mode can be selected by pressing the pushbutton CONST.FUEL on the front panel of the DGU. The intention with this function is to keep the fuel rack steady, the objective is to save fuel. The functions allows a greater variation of engine speed, and sets a larger deadband to the speed regulation. If the engine speed is outside the disengage high and low deadband, the function will be disengaged, and the governor will regulate the speed until it is inside the engage high and low deadband, as shown in the below drawing:


img6


1.4.4       ROUGH SEA mode

This mode can be selected by pressing the pushbutton ROUGH SEA on the front panel of the DGU. In this mode, the regulator selects the Rough Sea gain-setting for PI governor, and can also include the D-function (to make it a PID and not just a PI regulator). These alternate values may be programmed to adapt more to a special sea-going condition, such as ballasted vessel, or rough sea situations


1.4.5       SETPOINT mode

This mode can be selected by pressing the pushbutton FUEL SETP. on the front panel of the DGU. Enabling of setpoint mode is possible to prevent with a parameter setting. However, if the setpoint mode parameter is enabled, then setpoint mode can be transferred from Normal or Idle mode. This is done by opening the Change Lock switch to open position with the key and pushing the FUEL SETPOINT button on front panel. Note, however, that this is meant to be a degraded operational mode, where the command handle outputs a fuel-index command directly. This feature allows emergency operation from a more comfortable place than local stand at the engine side. When this function is in use, there will be a SYSTEM IN TEST alarm.


NOTE:        This mode has two more parameters that must be adjusted to match "RPM command" with "fuel index". Normal adjustment will be Dead Slow RPM level to match 0% fuel index and Full Seaspeed to match 100% fuel index.


1.4.6       TEST mode

The Test mode may be initiated both from on-line (from Normal mode) or off-line (from Idle mode). In this mode, the input values to the system can be set directly from front panel. The system shall respond to these settings in same manner as original values from input transducers. When this function is in use, there will be a SYSTEM IN TEST alarm.

a)        Transfer from Normal mode is done by selecting one of the buttons in Test area of front panel: CMD, PITCH, or CHARGE.


NOTE:        RPM button (measured RPM on engine) is not allowed, since one assume running engine condition.


b)        Transfer from Idle mode is done by selecting parameter no.1, and adjust data value to 2. In this situation, also selection of RPM test button is allowed.


1.4.7       CALIBRATION mode

Calibration mode may be transferred from both Normal and Idle mode. In Normal, running mode the CAL test button starts an overlaying RPM value to the real inputted data. This "disturbance" value may be initiated in order to test governor response. Transfer from Idle mode is done by selecting parameter no.1 equal to 3. In this condition, an overlaying shifting signal adds to the value of chosen selection, either by pushing CMD-, RPM-, or CHARGE buttons.


1.4.8       SELFTEST mode

The Selftest mode can only be initiated from Idle mode condition. In this mode, the hardware memory of the computer is tested. Select parameter 1 and adjust data to 5 (light in indicator on panel). Then push the LAMP TEST button. The computer will respond with an "UP" status, or an "ERROR" status. Refer to Trouble Shooting if error status.


1.5                                            Programmable functions

The DGU regulating functions are to be set up with parameter values, in accordance with each particular installation. The main programmable functions are:


a)        Starting setpoints of fuel, and extension time after starting.


b)        Acceleration limiting of speed commanding signal.


c)        Critical speed-ranges.


d)        Maximum limit of RPM command value.


e)        Charge.air/index limiting characteristic.


f)        Speed/index limiting characteristic. (Torque Limiter)


g)        Zero-pitch/index limiting characteristic (only for CPP systems).


h)        Maximum limit of index (actuator) position.


i)        Regulator gain characteristics.


j)        Error-band gain setting.


k)        Command feed-forward influence in fuel setting.


l)        Filtering of speed oscillation caused by engine firing action (Notch filter).


In addition the system includes secondary programmable functions, such as:


m)        Numeric calibration of input data.


n)        Activity level-definitions of all binary input signals.


o)        Filtering of displayed data values.


p)        Data output on analog test-channels.


q)        Auto-calibration of actuator servo.


r)        Delay time in alarming condition to Alarm central.


1.6                                            Programming characteristics

Table 1.1 illustrates the regulators main programmable functions.


Function

Characteristics

Parameters

Comments

1.

Governor

Damping

img7

Gain (1)

Integration

Factor (2)

Increasing gain may speed up system response.

Increasing integration factor will increase relative stability

2.

Error-Band Suppression

img8

Deadband (1)

Band-Gain (2)

Band suppression mode is operator selectable. Suppresses vibration or jiggling of actuator system

3.

RPM Command

Forward

Coupling


img9

Forward Gain (1)

Direct increase or decrease of fuel index setting, irrespective of deadband in regulator system. Makes possible direct fuel control in speed detection failure situation

4.

Low-Speed

Vibratory

Revolution

Suppression

img10

Frequency

Factor (1)

The suppression filter will automatically be disconnected above maximum specified speed limit


Table 1.1 Regulator Conditioning Functions



1.7                                            Regulator main functions

The DGS 8800e system consists of two separate, and modular microprocessor controlled sub-systems performing the following functions:


        RPM Regulating Function.


        Fuel Actuating Function.


A simplified block diagram of the DGS 8800e system is shown in Fig. 1.7.



img11


Figure 1.7 DGU 8800e Block Diagram.



1.7.1       RPM Controller Function

The RPM reference values are automatically computed for all engine running conditions, such as start/stop, slow-down, emergency run, and normal running. The RPM measurements are converted from pulse frequency data to filtered, digital internal values.


The difference between reference and measurement is processed to ensure the optimum correction signal to the fuel setting, taking both the loading characteristics and running RPM into account.


Maximum fuel is automatically limited according to tolerances given by speed and charge air pressure.


The RPM Regulating Functions are shown in Fig. 1.8 and detailed in Fig. 1.9 to 1.13.


img12


Figure 1.8 Governor functions.




1.7.2       RPM Command Function


        Commanding input signal either from remote control system, local control panel, and control room back-up panel (optionally).


        The operator may reduce the maximum allowed speed by programming the command Limiting Function.


        System control inputs automatically select "failure-mode" commanding reference, such as slow-down or back-up RPM.


        Rate Limiting Function enables the operator to restrict engine acceleration or retardation.


        Critical Speed Discrimination results in switch transfer of speed reference signal through the barred range.


        Start - Stop Function automatically selects fuel-setting reference, with automatic transfer to speed setting reference.




img13

Figure 1.9 RPM Command Function.


1.7.3       RPM Measurement Function


        Pick-up pulses are converted to actual data value. The only scaling factor is the number of teeths on the gearwheel (pulses generated for one revolution of the engine).

        Channels A and B are tested for validity, with automatic selection of correct channel.

        Automatic filtering of low-speed torsional vibratory noise measurement.

        High frequency filtering of speed measurement.

        Additional filtering and measured data to adapt to numeric display.


img14

Figure 1.10 RPM Measuring Function.


1.7.4       
Regulator Gain Function


        Error Band signal gain reduction to suppress low amplitude noise. Deadband selectable.

        Governor common-gain adjusting function, to select proper damping.

        Automatic adjustment of system integrating gain according to engine operating data.

        Automatic adjustment of common gain according to engine operating speed.



img15


Figure 1.11 Regulating Gain Function.


1.7.5       Fuel Limiting Function

        Limiting of fuel setting according to engine propeller load characteristic.

        Limiting of fuel setting according to charge air pressure curve.

        Low pitch fuel limiting, mainly to limit index when restart from Bridge control (CPP-systems).

        Manual limiting to fix the absolute maximum allowed fuel setting.

        Selecting function, always to transmit the lowest of limited values.

        Non linear compensation due to actuator position.

        Non linear compensation due to fuel pump leaking when low engine speed

        Scaling function, to match the actuator input signal and fuel pump offset values.




img16


Figure 1.12 Fuel Limiting, Non Linear Compensation and Output Scaling Function


1.8                                            Actuator Main Functions

1.8.1       Fuel Actuating Function

The signal processing in DGU acts to enable the actuator to follow-up command signals as fast as possible. Electrical on/off signals are connected to the electric actuator. Position feedback signal from actuator indicates the actual position of servo.


1.8.2       Servo Control function

The main sub functions are:


        Adjustable Servo PI controller.

        Output Scaling for signal adaption to the Motor Servo Amplifier.

        Monitoring control signals, and in case of failure, block the actuator.

        Distribute fuel-indication to user (options).




img17



Figure 1.13 Servo Control Function



2.                                            System Operation

2.1                                            Regulator Operator Panel

2.1.1       Panel Layout

The functional layout of DGU panel is shown in Fig. 2.1. The grouping of functions are the same for the Regulator Part (left) and Actuator part (right). The following paragraphs include more detailed description.


Note that the panel has a removable change lock key. The key has to be in the OPEN position to be able to change the most critical system parameters. In addition, a special "service code" must be set to ensure that only authorized personnel are able to modify the system parameters.


img18


Figure 2.1 Operator Panel


2.1.2       Regulator Indicator Lamps


img19


Figure 2.2 Indicator lamps.


2.1.3       Regulator Mode Lamps

Indicate the main constraints under which the regulator function is operating.


NORMAL        Normal regulating mode with real process input and output data from engine. Selection of this mode is done automatically when Cmd Handle is moved out of stop. Simulations of RPM command and Scavenge air pressure is possible when Change Lock is in Open position, also if engine is running. Simulation of Measured RPM is not possible in this mode.


IDLE        Idle mode is automatically selected when RPM command handle is in stop position. All data is still monitored. The mode is now possible to change to Test, Calibrate and Self test. This is done by selecting parameter 1 (Mode select) and adjusting the data value to different values. (Alarm indication "System in Test" will lit and alarm is given to the alarm-central).


SETPOINT        Direct Fuel Control mode, regardless of Measured RPM. This mode is selected when the push-button "Fuel Setpoint" is pushed and the Change Lock is in Open position. Use caution if this is done while the engine is running. This mode is a bypass function of the regulator and is normally only used to test the actuator performance.


TEST        Test mode is only selectable if command handle is in stop. System may be set-up with all input data simulated, instead of real sensors.


CALIBRATE        System may be set-up with special calibration signals or routines. Calibrate will also lit up if the "CAL" button is activated.


SELF TEST        Self testing of computer memory is activated by pushing LAMP TEST. This will respond with "rEG-UP" if memory is ok or with "Error" if there are any memory problems. Ref. Trouble Shooting, chapter 3.


2.1.4       Regulator STATUS lamps

Indicate a running condition that restricts or reflects system performance.


REGULATOR ON        System in running status. Regulation of fuel index on engine.


START        Starting phase is activated. Fixed fuel in start position.


STOP        System in "Engine-Stop" condition. Rpm Cmd setpoint is Zero.


RPM LIMIT ON        RPM Command setting is restricted by a limiting condition, such as manual limit setting, or a critical speed range (flashing).


FUEL LIMIT ON        Regulating fuel output is restricted by automatic limiting causes, such as manual limit setting, speed limiting, or scavenge air limiting. Engine is not allowed to have more fuel.


OTHER        "Other" will indirectly reflect a status that can be pin-pointed by selecting appropriate parameter number for display (Parameter 9).


2.1.5       Regulator ALARM/WARNING lamps

Indicate the causes of any automatic locking of the system operation. Give

warnings about malfunctions.


LOW VOLTAGE        Indicates too low voltage in one of 4 power systems: +5V, +15V, -15V, +24V. Detailed information is given by LED indicator on adaptor Card. Ref. trouble shooting, chapter 3.


RPM DETECT FAIL        RPM detector (pick-up system) hardware failure. Detailed information is given by LED indicator on adaptor cards and on parameter 16. Ref. trouble shooting table, chapter 3.


IN-DATA ERROR        Analog input signal failure on RPM Cmd Handle in Control-room, RPM Cmd Handle on Bridge or scavenge air sensor on engine Ref. trouble shooting.


OUT-DATA ERROR        Communication failure between regulator card and actuator card. Ref. trouble shooting.


SYSTEM IN TEST        Indicates that system is in test or calibration mode.


OTHER        "Other" will indirectly reflect 'old Alarms' that has disappeared but is not reset by parameter 16 or 17.These two parameters will indicate which alarms that was activated. Parameter 10 will indicate "old-AL" if selected. Other Alarm will not give alarm to alarm-central since the failure is no longer there.


2.2                                            Parameter and Data Areas

2.2.1       Parameter Up/Down

In the parameter area, a set of relevant parameters together with their identification numbers, are listed. After selecting a number by using the up/down buttons in the parameter area, a value will appear on the data display. Fig. 2.3


img20


Figure 2.3 Regulator Parameter and Data Areas.


2.2.2       Data value Up/Down

Some data is Readable (like: RPM Command, Measured RPM, Charge air Pressure,,,) and some data is Adjustable (like: RPM limiter level,Fuel limiter level, Deadband,,,). The data value can be adjusted if the selected parameter is adjustable, this is achieved by pressing the "UP" or "DOWN" button in the data value section. The adjusted value will take effect immediately.


Adjustments is protected by the "Change Lock" and the "Service code", except parameter 6,7,8,14,16 and 17 (ref. parameter list).


2.2.3       Change Lock

Some parameters and some push-button may be changed/pushed only when the Commissioning Key is installed and turned to the "open" position.


2.2.4       Service code

Most critical parameters have additional safety locking by a "service code" that must be set. This service code is a special parameter that has to be set to a special value. A complete set of parameters is provided in the commissioning lists.


2.2.5       Save

Before powering off the 24 Volt, adjusted data can be saved by pressing the "SAVE" button, when the Change Lock is in Open position. If save is not pressed after an adjustment, the "old adjustments" will appear next time the power-supply has been off and then on again.


2.3                                            Regulator Operating Buttons

How to change regulating function in running conditions. Each button has its own on/off LED indicator. The indicator signal is feed back to the panel from the computer, in response to button operation. The buttons are showed in Fig. 2.4.


Note that DEAD BAND and ROUGH SEA buttons may be selected with no restriction. The FUEL SETPOINT button may be operated only when the key-lock is unlocked and the function parameter is enabled.


2.3.1       Constant Fuel Mode Button

On:        If LED on push button is lit then deadband is real (flat). The Constant Fuel Mode function reduces the motions of the governor. When engine speed is within the deadband limits, there is no movement of fuel rack. This function will cause more variations and also a possible constant deviation on the engine speed. Deadband value is adjustable on parameter no. 8 and is usually set to 2 RPM for normal running at sea. This value can be increased for more stabile actuator. However, special plant consideration may limit practical use of this function if there is an shaft generator or similar equipment.


Off:        If LED is not activated, the regulator will work with a reduced gain in the deadband zone. The reduction is adjustable and called "Reduction Gain". Reduction-factor of 5 means that the activity of actuator is reduced with 5 times. A deadband value of 2 means ± 2 RPM.


2.3.2       Rough Sea Button

On:        If led on the Rough Sea button is activated, the regulator selects the Rough Sea gain-setting for PI governor. Ref. parameter list. In addition the regulator can connect a Derivative function making the governor a PID regulator. The D-function is selected on parameter 73 "D-gain On/Off". These alternate values may be programmed to adapt more to a special sea-going condition, such as ballasted vessel, or rough sea situations.


Off:        If led on the Rough Sea button is not activated, the regulator selects the "normal" PI governor settings.


2.3.3       Fuel Setpoint Button

This function is under the Change Lock, so the Key is necessary to activate this function!


On:        Transfer the system mode unconditionally to NORMAL and SETPOINT. In setpoint mode, the fuel index is directly set by the Commanding RPM Handle. Setting the RPM Cmd Handle to "Dead Slow" will give 0% fuel and "Full" will give 100% fuel, independent of the engine speed. The scaling of this function can be done at fuel setpoint parameters. The fuel limiters will still work so engine will not be overloaded with fuel, but it may easily be over-speeded. (See also fuel setpoint mode).


Off:        Regulator in normal regulating mode.


img21

Figure 2.4 Regulator Operation Buttons.



2.3.4       Regulator Test Buttons

The test buttons may be used in all system modes. Pressing one of the upper buttons makes it possible to input a data value directly from the panel. The simulated input will initially equal that of the transducer, then be increased or decreased by the (+) or (-) button, respectively.


To direct the adjustment to only one of the signals given, the relevant button has to be pressed for a short time. When the button lamp starts flashing, the adjustment of the selected data is possible. A long press of the button resets the data to the original source.


The adjustments are visual by selecting the appropriate parameter number. The RATE-button allows the adjustment to be slow or fast.



The parameters to be simulated are:


CMD

RPM Command input

Parameter 2

RPM

RPM Measured

Parameter 3 (not in NORMAL mode)

CHARGE AIR

Charge Air Pressure

Parameter 5



img22



Figure 2.5 Regulator Test Buttons.


Note that the CAL. button may be used in normal running mode to add an artificial square-wave noise in the RPM measurement. This is to be able to observe the regulating action of the governor.


2.4                                            Actuator Operating Panel

2.4.1       Actuator Indicator Lamps


img23


Figure 2.6 Actuator Indication lamps.


Any number of lamps may be lit at the same time. Operation of the lamps is as follows:


2.4.2       Actuator MODE lamps


NORMAL        System in normal, regulating, mode with real process input and output data.


IDLE        System in a "ready-to-go" mode, doing all monitoring and transferring of all input data.


TEST        System test and simulation mode, that allows input data to be simulated from operator panel instead of real sensor inputs.


CALIBRATE        Not used in this version.


SELFTEST        Self test of the microcomputer memory is activated by addressing button RESET / LAMP TEST.


2.4.3       Actuator STATUS lamps


SERVO ON        Servo operation is active.


MANUAL CONTR.        Actuator may be manually positioned by operating (+) and (-) test buttons.


EXTERNAL STOP        The servo command input is forced to STOP by external emergency-stop activation or Shut Down/Overspeed.


SERVO BLOCKED        The actuator is blocked, caused by a fatal system error condition.


OTHER        Other system status is flagged. Selection of appropriate parameter number gives additional information.


2.4.4       Actuator ALARM lamps


LOW VOLTAGE        Indicates too low voltage in one or more of the 4 power systems: +5V, +15V, -15V, +24V. Details are shown on LED indicators on adaptor card.


FEEDBACK FAIL        Feedback error caused by signal failure in actuator position measuring.


IN-DATA ERROR        Cluster of errors that may be detected by the input data self-test routines. Error decoding is shown if selecting the appropriate parameter number.


SERVO AMPL FAIL.        Failure in the servo amplifier system (DSU, SBS, ABS or actuator).


SYSTEM IN TEST        System in test or calibration mode.


OTHER        Other system alarm or warning is indicated. Selection of appropriate parameter number gives additional information.


2.4.5       Actuator Parameter and Data Areas

In the parameter area a set of relevant parameters, together with their identification numbers, are listed.


After selecting a number by using the up/down buttons in the parameter area, a value will appear on the data display. Fig. 2.7 shows an example of having selected the measured fuel output of the system, which displays a value of 50.0 pump index.


img24

Figure 2.7 Actuator Parameter and Data Areas.


The fuel output is measured input signal to the system. In such a case, no new value would appear in the data display if the operator tried the up/down buttons in the data area. For this to happen, the selected parameter must be of an adjustable type, such as no. 5.


The change key has to be in "unlocked" position to be able to change any parameter value. Most critical parameters have an additional safety-lock, by means of a "service code" to be set, having first selected the proper parameter number. A complete list of parameters is provided in the commissioning lists.